Troubleshooting
FOR MODELS: 3508631; 3508632; 5008631; 5008632; 6508631; 6508632
*Also applicable to Models equipped with an electric intermittent pilot system. (Continued on next page)
SYMPTOM
POSSIBLE CAUSE
CORRECTIVE ACTION
1. Pilot will not stay lit
after following lighting
instructions.
A. Thermocouple producing
insufficient millivolts.
Check pilot flame it must impinge on thermocouple. Pilot flame may be low or
blowing (high) causing safety to drop out. Pilot orifice or aerating hole may be plugged
(check for spiders, webs or other organic material). Be sure the thermocouple is fully
inserted in its bracket.
B. Loose or dirty
thermocouple
connection at gas valve.
Clean and/or tighten the thermocouple fitting at the connection to the valve.
C. Thermocouple defective.
Check thermocouple with millivolt meter it should generate approximately 30
millivolts when not connected to a load. When connected to a load, it should generate
approximately 14 millivolts. If below 7 millivolts, replace.
D. Thermomagnet pilot
safety defective
Replace gas valve after above is checked out.
E. Vent safety shutoff
device.
Check wiring connections from valve to the vent safety shutoff device. Be sure all
connections are tight. Check for blocked or incorrect venting.
2. Main burner will not
come ON - pilot
burning and
thermostat set for
heat.
A. Gas valve not turned ON
after lighting the pilot.
Turn gas valve knob to 'ON" position - if no main gas flow, proceed to Step. "B".
B. Electric power to furnace
turned OFF.
Check for line voltage at furnace - if okay and no main gas flow, proceed to Step "C".
C. Low voltage transformer
or limit switch defective.
Check for 24 volts at the low voltage terminals of the transformer. If no voltage, turn
OFF electric power to furnace. Remove one wire from limit switch and check for
continuity across both terminals. No continuity replace limit switch. With a good limit
switch back in the circuit and the electric power turned ON - if no voltage, replace
transformer. NOTE: Before replacing the transformer or limit switch, check wiring for
loose connections or broken wires and repair as needed. If voltage is present at
transformer, proceed to Step "D".
D. Wall thermostat
defective.
With thermostat set for heat (contacts closed) check for voltage at terminals on gas
valve. If no voltage is present replace defective thermostat. NOTE: Before replacing
thermostat, be sure to check the wiring from the furnace to thermostat for loose
connections or broken wires and replace as needed.
E. Burner orifice plugged.
Clean or replace orifice - if okay and still no gas flow to main burners, proceed to Step
"F".
F. Gas valve defective.
Replace defective gas valve.
3. Burner comes "ON"
but goes OFF before
blower turns ON.
A. Defective wiring.
Turn OFF electric power to furnace. Remove top front panel, fan shroud and blower
wheel. Refer to Wiring Diagram and check all wiring inside junction box. Remove
center front panel and check all wiring inside switch box containing fan, limit and
selector switches. Correct if necessary. If correct, proceed to Step "B".
NOTE: Selector switch used only on Models 5008731; 5008732; 6508731; 6508732.
B. Defective limit switch.
If burner goes OFF in less than five minutes from room temperature start, check limit
control switch. If detective, replace. NOTE: Blower should turn "ON" within three
minutes after burner is "ON" from a room temperature start. If not, proceed to Step
"C.
C. Defective motor (2-
speed).
Jumper across the fan switch, turn electric power ON, the motor should rotate. If a 2-
speed motor is used - jumper from "brown" terminal on the fan switch to #2 (red)
terminal on the selector switch, motor should rotate on "LOW" speed. Jumper from
same "brown" terminal on the fan switch to #3 (black) terminal on the selector switch,
motor should rotate on "HIGH" speed. Replace motor if defective.
D. Defective motor (1-
speed).
Jumper across fan switch, turn electric power ON, motor should rotate. Replace motor
if detective.
E. Detective fan switch.
If, after checking above possibilities, problem still exists, replace fan switch.
4. Burner comes "ON",
blower comes "ON",
but cycles "ON"
and "OFF" while
burner remains "ON".
A. Furnace not operating at
full rate.
Check for low gas pressure at gas valve - should be 4" W.C. for Natural Gas, 11" W.C.
for L.P. Gas. Check burner orifice.
5. Burner comes "ON",
blower comes "ON",
but burner cycles
"OFF" and "ON" with
blower "ON".
A. Furnace operating over-
rate.
Check for high gas pressure at gas valve - correct if necessary. See correct pressure
above.
B. Line voltage too low.
Check line voltage to motor, if below 115 volts motor will run too slow.
C. Recirculation.
Heated air discharging against an object causing recirculation, such as a hall
installation or a large piece of furniture within 4' of discharge.
D. Loss of circulating air
due to leakage.
Check header plate installation and proper use of gaskets. Repair as necessary.
6. Furnace operates but
turns "OFF" before
A. Thermostat location.
Check location of thermostat. It should not be in the path of warm air discharge from
the furnace, near a lamp, or above a TV set or stereo.